Wall Mount / FP-2500E

FP-2500E

Description

FP-2500E
up to 10m (33ft) flame / intrusion detection

A UV Flame sensor and wide angle PIR combined within a single compact housing, for safer indoor protection of your premises.

Features


  • high sensitivity ultraviolet flame sensor + wide angle intrusion PIR
  • dual ouput modes; AND/OR
  • forced output mode following continued flame detection
  • Alarm memory function
  • Multi-zone PIR technology provides pet immunity up to 20kg (40lbs)
  • PIR area adjustment
  • Detection timer

  
  

Details

  • Specifications
  • Downloads

Model FP-2500E
Detection system Ultraviolet rays detection (185~260nm)
Detection distance 10m (33ft) max. from 7cm (2.75") flame
Detection area angle Approx. 120 degrees conically
Detection setting Detection timer (1sec, 3sec)
Detection sensitivity (H: 100%, L: 50%)
* Detection sensitivity can be set in "Individual" ("OR") mode.
* H: 100% is fixed in "AND" mode.
Alarm LED (RED) Part of flame sensor
• Lighting at alarm (detection time + off delay Approx. 2 sec.)
• Blinking (3 min) and Lighting (47 min) at memory
Detection system Passive Infrared
Detection area Wide Angle 10m (33ft) Max. 29 pairs
Detection area angle adjustment 3 steps
Alarm LED (RED) Part of passive sensor
• Lighting at alarm (one shot, Approx. 2 sec.)
• Blinking (3 min) and Lighting (47 min) at memory
• Lighting at trouble.
Power supply 10-30VDC (non-polarity)
current consumption 20mA Max.
Alarm output
Individual mode
Flame sensor output (From alarm terminal 1)
• Dry contact relay (Semi-Conductor) (N.O./N.C. selectable)
• Contact operation: Detection time + off delay.(Approx.2sec.)
• Contact capacity :30V (AC/DC) 0.25AMax.(resistive load)
Passive sensor output (From alarm terminal 2)
• Dry contact relay (Semi-Conductor) (N.O./N.C. selectable)
• Contact operation: One shot (Approx. 2 sec.)
• Contact capacity: 30V(AC/DC) 0.25AMax.(resistive load)
AND mode
Alarm signal outputs from alarm terminal 1、2、 when both sensors detect during the selected time.
• Dry contact relay (Semi-Conductor) (N.O./N.C. selectable)
• Contact operation: Min. 2 sec. (Max. depends on AND mode timer setting)
• Contact capacity: 30V (AC/DC) 0.25A Max.(resistive load)
Tamper output Dry contact relay NC
(Activated when the front cover is detached)
Contact capacity: 30V (AC/DC) 0.1A Max. (resistive load)
Alarm memory Reset after blinking (3 min) and lighting (47 min)
(Operate flame and passive LED individually)
Ambient temperature range -15°C to +55°C (5°F to +131°F) without condensation
Mounting position Indoor wall surface (Ceiling with option attachment “BCW-401”)
Connections Self-up terminal
Weight Approx. 120g
Appearance Resin

Datasheet